PC-025A HEAT EXCHANGER TRAINER

SPECIFICATIONS :

Process Element    : Tube & shell type Industrial grade

HEAT EXCHANGER : 150 mm x 600 mm single pass 12 tubes  in SS 304 body & copper tubing with provision for mounting standard temp. transmitter. Mounded on MS powder coated structure.

Temp. Transmitter  : RTD PT-100  -50° C to 140° C  2 Nos. with output 4 – 20 mA

I-P Converter             :Input 4-20 mA, Output 3-15 PSI with standard connectivity

Control Valve             : Pneumatic control Valve ½” line size

VALVE TYPE          : Globe type, Equal percentage, fail to close.

LINE SIZE                : 15 mm

VALVE LIFT        : 28 mm

INLET Pr.                 : 4 Kg.

DIFF. Pr.                 : 4 Kg Max.

CONTROL Pr.          : 3 – 15 PSI

ACTUATION                 : Diaphragm Reverse actuated

                            Close on supply failure

PNEUMATIC                 : ¼” N.P.T.                                         

CONNECTION BODY   : CS SS-316

BONET TYPE          :Standard Vertical Mount

 

FRL Unit  : Air filter , regulator with  pressure gauge & standard connectivity

Rotameter : 2 Nos. of 600 LPH

Heater : 2 KW with temp. control facility Thyristorised DC Drive

PID Controller : PID Control with  RS-485 MODBUS  Protocol

PC Interface : RS-232 / RS-485 PC interface

Software   : BenixPro User interactive GUI software with Graphical on line Display or trends, Data storage & retrieval, Tabulation, Printing of  tables & graphs for off line analysis of data.

Panel & Structure  : MS powder coated vertical panel with all controls, connectivity & Indicator. Complete set up mounted on MS powder coated frame with castor wheel.

Water Tanks : SS 304 MOC sump & hot water tank with anti rust Float pumps  / mono-block pumps of suitable capacity.

Temperature  : 2 Nos. of 3 ½ digit panel mounted temp. indicators

Indicators Computer  : Standard Branded PC with TFT monitor (Optional)

Accessories Compressor : To be provided by user. (Optionally available)

Compatibility : Panel is provided with interface for external connections like  DCS / PLC

Manual : Detailed Instruction manual  including Operations & experiments.